Update - In November 2020 the 5th edition of the Code of Practice was published. For information about this update, check out our latest article on the IET Code of Practice, 5th edition.

Changes to the IET Code of Practice

April 2014

4 Editions of the IEE Code of Practice for In-Service Inspection and Testing of Electrical Equipment
Fig.1 Code of Practice editions

The Code of Practice for In-Service Inspection and Testing of Electrical Equipment was first published in 1994 by the IEE, Institution of Electrical Engineers. By the time the 4th edition was published in 2012, the IEE had a name change to the IET, Institution of Engineering and Technology. We often get asked if it's okay to use an earlier version of the Code of Practice for our PAT testing course, so I thought it would be useful to look at the changes that have been made to the guidance on PAT testing throughout the 4 editions.


Earth Continuity test

Earth Continuity table in 1st Edition
Fig.2 Earth Continuity table 1st edition

The 1st edition includes the standard (0.1 + R)Ω limit, but also has some additional limits: 0.5Ω including the supply cable for BS4533 Luminaires, and (0.5 + R)Ω for BS415 Mains Operated Electronic and Related Apparatus. In the 2nd edition the earth continuity table was dropped and the advice was a (0.1 + R)Ω limit for all equipment. There is no mention of flexing the the cable during the high current test in the earlier editions. The 3rd and 4th editions add the extra requirement that “the resistance measurement should be observed while flexing the cable.” Previously this was only a requirement for the low current tests in 1st and 2nd editions. The 3rd edition also introduces the terminology of ‘hard’ and ‘soft’ tests for the high and low current tests. We have some further information in our article about the earth continuity test.


Insulation Resistance test

Insulation Resistance table in 1st Edition
Fig.3 Insulation Resistance table 1st edition

The limits for the insulation resistance test are quite different in the 1st edition than they are in later versions. The 1st edition gives limits for both class 1 and class 2 equipment in both ‘As New’ and ‘In-service’ condition The limit for ‘In-service’ for class 1 is 0.5MΩ, and the limit for ‘In-service’ for class 2 is 1MΩ and a variety of ‘As New’ limits depending on equipment type. In the 2nd edition this has been simplified to just 1.0 MΩ for class 1, 2MΩ for class 2, and 0.3MΩ for class 1 heating & cooking greater than 3kW. A new option of a 250V dc Insulation test voltage for sensitive electronic equipment is introduced in the 3rd edition.


Leakage Current test

The 1st edition briefly mentions that the insulation resistance test may be substituted by an earth leakage measurement where the insulation test is not appropriate. It also gives an example of mineral insulated elements that may not meet the insulation resistance limits, and an earth leakage test could be used instead. There is no mention of the limits for leakage in this section, but Appendix IV on Routine Manufacturing Testing does give some limits: 3.5mA for Class 1 and 0.25 for Class 2.

In the 2nd edition a new section on leakage tests has been introduced: 15.6 Protective conductor / touch current measurement. This advises that it is used “as an alternative to the in-service insulation test for use if the insulation resistance test either cannot be carried out or gives suspect test results.” It also includes a table for the leakage limits. The 3rd & 4th editions remain pretty much the same, however it now described as an “alternative or complimentary" test. We have some further information in our article about carrying out a leakage test.

Substitute/Alternative Leakage Test

The substitute leakage test was first introduced in the 3rd edition in section 10.1. The previous versions have no mention of this test.

Labels

The advice on PAT labels was pretty consistent in the 1st, 2nd, & 3rd editions. “The date on which re-testing is due or the last test date and re-test period should be stated”. This seems like a sensible approach; a user can look at the PAT label and be able to determine if a re-test is due. In the 4th edition there was a complete u-turn on this. The new advice is “The date for re-testing should not be marked on the label”. The 4th edition was introduced after the Professor Löfstedt Report on health and safety legislation recognised that there was an over compliance in PAT testing. This was partially due to PAT contractors often putting annual re-test dates on all labels.

Frequency of testing

The Suggested Initial Frequency of Inspection and Testing of Equipment table remained unchanged in the 1st, 2nd, & 3rd editions. The general advice on the frequency of testing in the 4th edition has been expanded to emphasis the need for a risk assessment approach to determine the re-test frequency. The table on suggested initial intervals is still included, albeit with some minor changes to some of the periods. It also has some new rows for fixed equipment.

Microwave oven leakage

Microwave section in 3rd edition
Fig.4 Microwave testing in 3rd edition

The 1st edition has a section on Microwave ovens (15.10). This states that microwave leakage (radiation) can occur if the oven is damaged or corroded but microwave leakage tests are normally only carried out after repair. The 2nd edition gives some information on functional checks, but no mention of microwave leakage tests. The 3rd edition recommends that “Microwave leakage should be checked at appropriate intervals”. The 4th edition dropped the microwave section completely. The preface gives details that the microwave leakage testing is not within the remit of the CoP as it is not an electrical safety test and for this reason it has been removed. Although this is no longer a PAT requirement, we do have an article on carrying out a microwave leakage test.


RCDs

As far as I can see, there is no mention of RCDs in the 1st & 2nd editions. In the 3rd edition it states that “The RCD should be checked for correct operation by plugging it in, switching it on and then pushing the test button.” It also recommends that the trip time is measured. In the 4th edition the wording for the trip time test has been changed and is now a requirement: “timing tests should take place during the combined inspection and testing.” Table 15.5 on RCD operating characteristics has also been updated.

Production testing

The 1st, 2nd, & 3rd editions all have a large section in the appendix dedicated to Production Testing. The reason given for its inclusion is that these tests may be required after the repair or refurbishment of equipment. In the 4th edition this entire section of the appendix has been dropped. The preface in the 4th edition explains “Production testing, previously included in this Code of Practice, has been removed as it is not relevant to in-service inspection and testing.”

Sections introduced in 2nd edition

The other notable additions to the 2nd edition are new sections on the Replacement of Appliance Flexes (15.13), and Plug Fuses (15.14)

Sections introduced in 3rd edition

New colour diagrams in 3rd edition
Fig.5 New colour diagrams in 3rd edition

From a reader's perspectve, the 3rd edition is a big improvement on the 2 earlier versions. It now includes useful colour diagrams throughout. The colour illustrations in appendix VIII showing examples and information for the visual inspection are a good addition.


Sections introduced in 4th edition

The 4th edition has a new chapter - 16. This includes some useful information that was missing in previous versions on New Equipment (16.1), Second-hand Equipment (16.2), and Hired Equipment (16.3).

Purchasing the Code of Practice

Code of Practice 4th Edition
Fig.6 Code of Practice 4th edition

If you are buying a copy of the Code of Practice for the City & Guilds PAT course, make sure you get the latest 4th edition; there are still some online retailers selling the old 3rd edition. The current C&G 2377-22 syllabus and exam is based on the 4th edition. The IET Code of Practice for In-Service Inspection and Testing of Electrical Equipment. 4th edition (ISBN 978-1-84919-626-0). Second hand copies sometimes come up on Ebay, but just make sure that all the pages are intact, the binding quality on the early print runs of the 4th edition was terrible, so many have missing pages.


5th Edition Update!

New 5th edition published November 2020
Fig.6 New 5th edition - November 2020

In November 2020, the 4th edition was replaced with a new 5th edition. The City & Guilds PAT testing qualification was also updated to reflect the changes in the new edition. The new City & Guilds qualification is 2377-77 and it is still open book, so you will need the latest 5th edition of the IET for the exam. We also have a new article on the IET Code of Practice, 5th edition.